1000GH

by Hinode Electric

Features

  • A fuse with optional indicator that shows evidence of operation
  • Compliant to 1000V DC
  • It is also effective with high blocking performance for systems operating at 400V

Rating

Rated voltage and blocking capacity 1000V AC-100KA
Minimum block-off current 1000V AC/DC - 6 times the rated amperage
Maximum arc voltage 2000V
 
CAUTION

When purchasing a product with an indicator fuse, enter "S" immediately after the amperage rating in the product name (e.g. 1000GH-200SUL)

UL/cUL Standard Approved Rating

When applying the standard to UL standard approved items, use the fuse in the following rating.

Rated voltage and blocking capacity Same as the standard rating

 

Standard Specifications

TYPEAmpere RatingPre-arc I²t (A²S)Total I²t (A²S) at AC660V100KAWatts-Lss (W)
1000GH-16 16A 20 230 3.6
1000GH-20 20A 30 350 4.5
1000GH-25 25A 50 600 5.0
1000GH-32 32A 85 900 6.0
1000GH-40 40A 145 1400 8.0
1000GH-50 50A 230 2300 12
1000GH-63 63A 330 3200 25
1000GH-80 80A 580 5500 28
1000GH-100 100A 1000 8500 30
1000GH-125 125A 1650 15500 42
1000GH-160 160A 2500 22000 65
1000GH-200 200A 4000 35000 75
1000GH-250 250A 6600 62000 90
1000GH-315 315A 10000 90000 120
1000GH-400 400A 16000 145000 155
1000GH-500 500A 26400 250000 190
1000GH-630 630A 39500 370000 250

*** ALL FUSES ARE AVAILABLE WITH TRIP INDICATOR - BY ADDING 'S' TO THE END OF THE MODEL TYPE ***