250GH/350GH

by Hinode Electric

Features

  • A fuse with optional indicator that shows evidence of operation
  • Durable against repetitive current
  • Compliant to 400V DC (350GH)
  • Compliant with various standards

Rating

250GH

Rated voltage and breaking capacity 250V AC-100kA, 250V DC (L/R = 10ms)-100kA
Minimum breaking current 250V AC/DC - 5 times the rated amperage
Maximum arc voltage 500V

350GH

Rated voltage and breaking capacity 250/350V AC-100kA, 400V DC (L/R=2ms)-10kA
Minimum breaking current 350V AC /400V DC - 5 times the rated amperage
Maximum arc voltage 700V
 
CAUTION
  1. When purchasing a product with an indicator fuse, enter "S" immediately after the amperage rating in the product name (e.g. 350GH-200SUL)
  2. The minimum working voltage of the indicator fuse is 10V

UL/cUL Standard Approved Rating

When applying the standard to UL standard approved items, use the fuse in the following rating.

2560GH (cUL not approved)

Rated voltage and breaking capacity 250V AC-100kA, 250V DC (L/R = 10ms)-100kA

350GH

Rated voltage and breaking capacity 380V AC-10kA, 400V DC (L/R = 2ms)-10kA

CCC Standard Approved Rating

When applying the standard to CCC standard approved items, use the fuse in the following rating.

350GH

Rated voltage and breaking capacity 350V AC-50kA, 250V DC (L/R = 15ms)-50kA