KDR line reactors prevent nuisance tripping
  • Limits expensive down-time
KDR line reactors reduce harmonic current
  • Increases life of drive
  • Protects sensitive equipment 
Power quality has degraded over time due to the increased use of non-linear loads. Drives and other sensitive devices are vulnerable to electrical distortion on the line. The KDR line reactor provides a cost-effective solution to this issue.

Harmonics and Power Quality

Variable frequency drives are beneficial to a wide range of applications, but contain a power conversion process that creates current and voltage distortion which can cause system-wide problems, including:
  • Transformer and distribution equipment overheating
  • Random breaker tripping
  • Sensitive equipment may fail completely
  • Poor power factor
  • Reduced system efficiency

KDR Optimized Line Reactor on Harmonics

The addition of a KDR Reactor will reduce harmonic content, which reduces the total RMS current, thereby improving the total power factor.
  • Nuisance tripping is less common
  • Drive uptime is increased
  • Power factor is improved
Harmonic Current without KDR
 
 
Harmonic Current with KDR
 

Transient Voltages Cause Nuisance Tripping

A voltage transient, commonly caused by capacitor bank switching (or other issues), sends a current surge into the VFD bus capacitor. The additional current raises bus voltage, thus causing a drive fault (trip). In addition, this overvoltage condition will cause the drive to shut down in order to protect its components.

KDR Optimized Line Reactor on Transient Voltages

The additional impedance offered by the KDR Line Reactor slows down the current surge, thus reducing the likelihood of the drive tripping offline.
 
Voltage Before KDR
 
 
Voltage After KDR
 

Unbalanced Distribution Systems Cause Nuisance Tripping

Input voltage phase unbalance may prevent the drive from performing due to subsequent overcurrent conditions which cause the drive to cease operating.

KDR Optimized Line Reactor on Unbalanced systems

The addition of a KDR Reactor to the input of every drive will help balance the drive input line currents.
 
Extend the life of the motor on the Output:
  • Dampen Overshoot Peak Voltage
  • Reduce Motor Heating
  • Reduce Audible Noise 

DIN Rail Line Reactor Option

For smaller applications incorporate DIN Rail Drive Reactors to the input and output of PWM drives for easy installation and superior performance:
  • Reduce installation time and cost
  • Compatible with any 35mm DIN Rail
  • Mounts to “Standard Steel High Profile” or “Heavy Duty Steel” DIN Rails
  • Reactor mounts horizontally on horizontal DIN Rail
  • Improves organization of reactors and their cabling
  • RoHS compliant

Single-Phase Line Reactor Applications

KDR Line Reactors can be used in single-phase applications. Please note that the level of impedance will be reduced from three-phase levels. Contact Technical Support 800-824-8282 for more information.

Universal Mounting Footprint

For more information on the Universal Mounting footprint, see the following documents:

Impedance Options

The KDR Line Reactor has been designed to provide the best protection for both your drive and your application. KDR Line Reactors are available in two ratings versions, Low “Z” (low impedance) and High “Z” (high impedance). Input impedance can significantly improve drive performance. Select impedance based on the guidelines below:

Use KDR Low “Z” Units For:

Any application where either a 1.5% or 3% reactor would be applied.
 
Reduction of nuisance tripping caused by:
  • Transient voltages caused by capacitor switching
  • Line notching
  • DC bus overvoltage tripping
  • Inverter overcurrent and overvoltage

Additional benefits include:

  • Lowering injected percentage of harmonic current
  • Improving true power factor
  • Reducing cross-talk between drives
  • Adding impedance to drives with DC link chokes/reactors when more impedance is desired due to a relatively stiff source

Use KDR High “Z” Units For:

Any application where a 5% reactor would be applied.
 
KDR High “Z” offers the same superior benefits as Low “Z” plus additional benefits which include:
  • Helping prevent drive component damage
  • Providing maximum harmonic mitigation without adding capacitance
  • Further improving true power factor
  • Adding impedance to drives without DC link chokes/reactors when more impedance is desired due to a relatively stiff source

KDR Specifications

Impedance Protection Low “Z” and High “Z”
System Voltage 208/240 VAC, 480 VAC, 575/600 VAC, 690 VAC
Ambient Temperature 50° C (122° F) - Open; 40° C (104° F) - Enclosed
Altitude (Maximum) 2,000 meters (6,000 feet)
Derating necessary above 2,000 meters
Fundamental Frequency 50/60 Hz
Short Term Overload Rating Tolerate 200% rated I for a minimum of 3 minutes
Agency Approvals cUL, UL; UL Recognized, CE Marked
Inductance Characteristics
Minimum 95% L at 110% Load
Minimum 80% L at 150% Load
Input and Output Available for either the line or load side of a VFD
Enclosures Open, UL Type 1, UL Type 3R
 

KDR Typical Applications

  • Oil and Gas Pumps
  • Irrigation Fields, Farms
  • Water, Wastewater
  • HVAC
  • Steel Industry
  • Pulp/Paper
  • Machining
  • Extruders